Technical Data | 6ES7331-1KF02-0AB0 | 6ES7331-7KF02-0AB0 | |
Price | USD180.00 | USD 155.00 | |
Input current | |||
from backplane bus 5 V DC, max. | 90 mA | 50 mA | |
Power loss, typ. | 0.4 W | 1 W | |
Analog inputs | |||
Number of analog inputs | 8 | 8 | |
● For resistance measurement | 8 | 4 | |
permissible input voltage for voltage input (destruction limit), max. | 30 V; 12 V continuous, 30 V for max. 1 s | 20 V; continuous; 75 V for max. 1 s | |
Input ranges (rated values), voltages |
|||
0 to +10 V | Yes | No | |
Input resistance (0 to 10 V) | 100 kΩ | 100 kΩ | |
1 V to 5 V | Yes | No | |
Input resistance (1 V to 5 V) | 100 kΩ | Yes | |
1 V to 10 V | No | 10 MΩ | |
-1 V to +1 V | Yes | Yes | |
Input resistance (-1 V to +1 V) | 100 kΩ | 100 kΩ | |
-10 V to +10 V | Yes | Yes | |
Input resistance (-10 V to +10 V) | 100 kΩ | 100 kΩ | |
-250 mV to +250 mV | No | Yes | |
Input resistance (-5 V to +5 V) | 100 kΩ | 10 MΩ | |
-50 mV to +50 mV | Yes | Yes | |
Input resistance (-50 mV to +50 mV) | 100 kΩ | 100 kΩ | |
-500 mV to +500 mV | Yes | No | |
Input resistance (-500 mV to +500 mV) | 100 kΩ | Yes | |
-80 mV to +80 mV | No | 10 MΩ | |
Input ranges (rated values), currents | |||
0 to 20 mA | Yes | Yes | |
Input resistance (0 to 20 mA) | 100 Ω | 25 Ω | |
-10 mA to +10 mA | No | Yes | |
-20 mA to +20 mA | Yes | 25 Ω | |
Input resistance (-20 mA to +20 mA) | 100 Ω | Yes | |
-3.2 mA to +3.2 mA | No | 25 Ω | |
4 mA to 20 mA | Yes | Yes | |
Input resistance (4 mA to 20 mA) | 100 Ω | 25 Ω | |
Input ranges (rated values), thermocouples | Input ranges (rated values), thermocouples | ||
Input ranges (rated values), resistance thermometer |
|||
Cu 10 | No | No | |
Ni 100 | Yes; Standard/climate | Yes; Standard | |
Input resistance (Ni 100) | 100 MΩ | 10 MΩ | |
Ni 1000 | Yes | No | |
Input resistance (Ni 1000) | 100 MΩ | No | |
LG-Ni 1000 | Yes; Standard/climate | No | |
Input resistance (LG-Ni 1000) | 100 MΩ | No | |
Ni 200 | No | Yes; Standard | |
Ni 500 | No | 10 MΩ | |
Pt 100 | Yes; Standard/climate | No | |
Input resistance (Pt 100) | 100 MΩ | No | |
Pt 1000 | No | No | |
Input ranges (rated values), resistors | |||
zero to 150 ohms | No | Yes | |
0 to 300 ohms | No | 10 MΩ | |
0 to 600 ohms | Yes | Yes | |
Input resistance (0 to 600 ohms) | 100 MΩ | 10 MΩ | |
0 to 6000 ohms | Yes | Yes | |
Input resistance (0 to 6000 ohms) | 100 MΩ | 10 MΩ | |
Thermocouple (TC) | |||
Temperature compensation |
|||
parameterizable | No | Yes | |
internal temperature compensation | No | Yes | |
external temperature compensation with compensations socket | No | Yes | |
Characteristic linearization | |||
● parameterizable | Yes | Yes | |
— for thermocouples | No | Type E, J, K, L, N | |
— for resistance thermometer | yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con. | Pt100 (standard, climatic range), Ni100 (standard, climatic range) | |
Cable length | |||
● shielded, max. | 200 m; max. 50 m at 50 mV | 200 m; 50 m at 80 mV and thermocouples | |
Analog value generation for the inputs | |||
Measurement principle | integrating | integrating | |
Integration and conversion time/resolution per channel | |||
Resolution with overrange (bit including sign), max. | 13 bit | 15 bit; Unipolar: 9/12/12/14 bit; bipolar: 9 bit + sign/12 bit + sign/12 bit + sign/14 bit + sign | |
Integration time, parameterizable | Yes; 60 / 50 ms | Yes; 2,5 / 16,67 / 20 / 100 ms | |
Basic conversion time (ms) | 66 / 55 ms | 3 / 17 / 22 / 102 ms | |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz | 400 / 60 / 50 / 10 Hz | |
Interrupts/diagnostics/status information |
|||
Diagnostic functions | No | Yes; Parameterizable | |
Alarms | |||
Diagnostic alarm | No | Yes; Parameterizable, channels 0 and 2 | |
Limit value alarm | No | Yes; Parameterizable | |
Diagnostic messages | |||
Diagnostic information readable | No | Yes | |
Indication LED | |||
Group error SF (red) | No | Yes | |
Potential separation | |||
Potential separation analog inputs | |||
between the channels and backplane bus | Yes | Yes | |
Isolation | |||
Isolation tested with | 500 V DC | 500 V DC | |
Connection method | |||
required front connector | 40-pin | 20-pin | |
Dimensions |
|||
Width | 40 mm | 40 mm | |
Height | 125 mm | 125 mm | |
Depth | 117 mm | 117 mm | |
Weight, approx. | 250 g | 250 g |